Min forward angle
10
88 deg
85 deg
73 deg
100% of In
20% of In
1% of In
GUID-F9F1619D-E1B5-4650-A5CB-B62A7F6B0A90 V2 EN
Figure 157:
Phase angle 88 amplitude (Directional mode = Forward)
4.2.2.9
Application
The directional earth-fault protection (F)DEFxPDEF is designed for protection and
clearance of earth faults and for earth-fault protection of different equipment
connected to the power systems, such as shunt capacitor banks or shunt reactors, and
for backup earth-fault protection of power transformers.
Many applications require several steps using different current start levels and time
delays. (F)DEFxPDEF consists of two different stages.
•
Low (F)DEFLPDEF
•
High DEFHPDEF
(F)DEFLPDEF contains several types of time delay characteristics. DEFHPDEF is
used for fast clearance of serious earth faults.
The protection can be based on the phase angle criterion with extended operating
sector. It can also be based on measuring either the reactive part Iosin(φ) or the active
part Iocos(φ) of the residual current. In isolated networks or in networks with high
impedance earthing, the phase-to-earth fault current is significantly smaller than the
short-circuit currents. In addition, the magnitude of the fault current is almost
independent of the fault location in the network.
The function uses the residual current components Iocos(φ) or Iosin(φ) according to
the earthing method, where φ is the angle between the residual current and the
reference residual voltage (-Uo). In compensated networks, the phase angle criterion
with extended operating sector can also be used. When the relay characteristic angle
RCA is 0 degrees, the negative quadrant of the operation sector can be extended with
the
Min forward angle
setting. The operation sector can be set between 0 and -180
degrees, so that the total operation sector is from +90 to -180 degrees. In other words,
the sector can be up to 270 degrees wide. This allows the protection settings to stay the
Section 4
1MRS758755 A
Protection functions
302
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...