The maximum three-second or ten-minute mean voltage unbalance is recorded during
the active observation period. The observation period start time
PR_STR_TIME
,
observation period end time
PR_END_TIME
, maximum voltage unbalance value
during observation period active,
MAX_UNB_VAL
and time of occurrence
MAX_UNB_TIME
are available through the Monitored data view. These outputs are
updated once
OBS_PR_ACT
deactivates.
Percentile calculator
The purpose of the Percentile calculator module is to find the voltage unbalance level
so that during the observation time 95 percent (default value of the
Percentile
unbalance
setting) of all the measured voltage unbalance amplitudes are less than or
equal to the calculated percentile.
The computed output value
PCT_UNB_VAL
, below which the percentile of the values
lies, is available in the Monitored data view. The
PCT_UNB_VAL
output value is
updated at the end of the observation period.
If the output
PCT_UNB_VAL
is higher than the defined setting
Unbalance start val
at
the end of the observation period, an alarm output
PCT_UNB_AL
is activated. The
PCT_UNB_AL
output remains active for the whole period before the next period
completes.
The
BLOCK
input blocks the output
PCT_UNB_VAL
.
Recorded data
The information required for a later fault analysis is stored when the Recorded data
module is triggered. This happens when a voltage unbalance is detected by the
Voltage unbalance detector module.
Three sets of recorded data are available in total. The sets are saved in data banks 1...3.
The data bank 1 holds the most recent recorded data. Older data are moved to the
subsequent banks (1 to 2 and 2 to 3) when a voltage unbalance is detected. When all
three banks have data and a new variation is detected, the latest data set is placed into
bank 1 and the data in bank 3 is overwritten by the data from bank 2.
The recorded data can be reset with the
RESET
binary input signal by navigating to the
HMI reset (
Main menu/Clear/Reset recorded data/VSQVUBx
) or through tools
via communications.
When a voltage unbalance is detected in the system, VSQVUB responds with the
MN_UNB_AL
alarm signal. During the alarm situation, VSQVUB stores the
maximum magnitude and the time of occurrence and the duration of alarm
MN_UNB_AL
. The recorded data is stored when
MN_UNB_AL
is deactivated.
Table 701:
Recorded data
Parameter
Description
Alarm high mean Dur
Time duration for alarm high mean unbalance
Max unbalance Volt
Maximum three-second voltage
Time Max Unb Volt
Time stamp of voltage unbalance
1MRS758755 A
Section 10
Power quality measurement functions
REC615 and RER615
703
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...