![ABB RELION Series Скачать руководство пользователя страница 121](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191121.webp)
GOOSERCV_ENUM function block does not receive the value from the sending
device or it is invalid, the default value (0) is used and the
ALARM
is activated in the
T_HEALTH function block.
3.15.4.3
Signals
Table 66:
T_HEALTH Input signals
Name
Type
Default
Description
IN1
Any
0
Input signal
Table 67:
T_HEALTH Output signals
Name
Type
Description
OK
BOOLEAN
Output signal
WARNING
BOOLEAN
Output signal
ALARM
BOOLEAN
Output signal
3.15.5
T_F32_INT8 function block
3.15.5.1
Function block
GUID-F0F44FBF-FB56-4BC2-B421-F1A7924E6B8C V1 EN
Figure 60:
Function block
3.15.5.2
Functionality
The T_F32_INT8 function is used to convert 32-bit floating type values to 8-bit
integer type. The rounding operation is included. Output value saturates if the input
value is below the minimum or above the maximum value. .
3.15.5.3
Signals
Table 68:
T_F32_INT8 Input signals
Name
Type
Default
Description
F32
FLOAT32
0.0
Input signal
Table 69:
T_F32_INT8 Output signal
Name
Type
Description
INT8
INT8
Output signal
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
115
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...