The
START
output is activated once
Start delay time
has elapsed.
OPERATE
output is
activated once
Operate delay time
has elapsed and the above three conditions are
valid. Reset timer is started if any of the above three conditions is not valid. In case
fault is transient and self-extinguishes,
START
output stays activated until the elapse
of reset timer (setting Reset delay time). After
OPERATE
output activation,
START
and
OPERATE
outputs are reset immediately, if any of the above three conditions is
not valid. The start duration value START_DUR, available in the Monitored data
view, indicates the percentage ratio of the start situation and the set operating time.
In case detection of temporary earth faults is not desired, the activation
of
START
output can be delayed with setting
Start delay time
. The
same setting can be also used to avoid restarting of the function during
long lasting post-fault oscillations, if time constant of post-fault
oscillations is very long (network losses and damping is low).
To keep the operate timer activated between current spikes during
intermittent or restriking earth fault, the
Reset delay time
should be set
to a value exceeding the maximum expected time interval between
fault spikes (obtained at full resonance condition). Recommended
value is at least 300 ms.
Section 4
1MRS758755 A
Protection functions
386
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...