Example 2
: Both Io and Uo are calculated from the phase quantities. Phase CT-ratio
is 100 : 1 A and phase VT-ratio is 20/sqrt(3) kV : 100/sqrt(3) V. In this case,
"Calculated Io" and "Calculated Uo" are selected. The nominal values for residual
current and residual voltage are obtained from CT and VT ratios entered in Residual
current Io:
Configuration/Analog inputs/Current (3I,CT)
: 100 A : 1 A. The
residual voltage Uo:
Configuration/Analog inputs/Voltage (3U,VT)
: 20.000 kV :
100 V. The
Start value
of 1.0 × In corresponds to 1.0 * 100 A = 100 A in the primary.
The
Voltage start value
of 1.0 × Un corresponds to 1.0 * 20.000 kV = 20.000 kV in the
primary.
If "Calculated Uo" is selected, the residual voltage nominal value is
always phase-to-phase voltage. Thus, the valid maximum setting for
residual Voltage start value is 0.577 x Un. The calculated Uo requires
that all the three phase-to-earth voltages are connected to the
protection relay. Uo cannot be calculated from the phase-to-phase
voltages.
If the
Enable voltage limit
setting is set to "True", the magnitude of the
polarizing quantity is checked even if the
Directional mode
was set to
"Non-directional" or
Allow Non Dir
to "True". The protection relay
does not accept the
Start value
or
Start value Mult
setting if the
product of these settings exceeds the
Start value
setting range.
Typically, the
ENA_MULT
input is connected to the inrush detection function
INRHPAR. In case of inrush, INRPHAR activates the
ENA_MULT
input, which
multiplies
Start value
by the
Start value Mult
setting.
Directional calculation
The directional calculation module monitors the angle between the polarizing
quantity and operating quantity. Depending on the
Pol quantity
setting, the polarizing
quantity can be the residual voltage (measured or calculated) or the negative sequence
voltage. When the angle is in the operation sector, the module sends the enabling
signal to the timer module.
The minimum signal level which allows the directional operation can be set with the
Min operate current
and
Min operate voltage
settings.
If
Pol quantity
is set to "Zero. seq. volt", the residual current and residual voltage are
used for directional calculation.
If
Pol quantity
is set to "Neg. seq. volt", the negative sequence current and negative
sequence voltage are used for directional calculation.
In the phasor diagrams representing the operation of (F)DEFxPDEF, the polarity of
the polarizing quantity (Uo or U2) is reversed, that is, the polarizing quantity in the
phasor diagrams is either -Uo or -U2. Reversing is done by switching the polarity of
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
281
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...