![ABB RELION Series Скачать руководство пользователя страница 700](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191700.webp)
10.3.8
Settings
Table 695:
PHQVVR Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Reference voltage
10.0...200.0
%Un
0.1
57.7
Reference supply voltage in %
Voltage dip set 1
10.0...100.0
%
0.1
80.0
Dip limit 1 in % of reference voltage
VVa dip time 1
0.5...54.0
cycles
0.1
3.0
Voltage variation dip duration 1
Voltage dip set 2
10.0...100.0
%
0.1
80.0
Dip limit 2 in % of reference voltage
VVa dip time 2
10.0...180.0
cycles
0.1
30.0
Voltage variation dip duration 2
Voltage dip set 3
10.0...100.0
%
0.1
80.0
Dip limit 3 in % of reference voltage
VVa dip time 3
2000...60000
ms
10
3000
Voltage variation dip duration 3
Voltage swell set 1
100.0...140.0
%
0.1
120.0
Swell limit 1 in % of reference voltage
VVa swell time 1
0.5...54.0
cycles
0.1
0.5
Voltage variation swell duration 1
Voltage swell set 2
100.0...140.0
%
0.1
120.0
Swell limit 2 in % of reference voltage
VVa swell time 2
10.0...80.0
cycles
0.1
10.0
Voltage variation swell duration 2
Voltage swell set 3
100.0...140.0
%
0.1
120.0
Swell limit 3 in % of reference voltage
VVa swell time 3
2000...60000
ms
10
2000
Voltage variation swell duration 3
Voltage Int set
0.0...100.0
%
0.1
10.0
Interruption limit in % of reference voltage
VVa Int time 1
0.5...30.0
cycles
0.1
3.0
Voltage variation Int duration 1
VVa Int time 2
10.0...180.0
cycles
0.1
30.0
Voltage variation Int duration 2
VVa Int time 3
2000...60000
ms
10
3000
Voltage variation interruption duration 3
VVa Dur Max
100...3600000
ms
100
60000
Maximum voltage variation duration
Table 696:
PHQVVR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Variation enable
1=Swell
2=Dip
3=Swell + dip
4=Interruption
5=Swell + Int
6=Dip + Int
7=Swell+dip+Int
7=Swell+dip+Int
Enable variation type
Table 697:
PHQVVR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase supervision
1=Ph A
2=Ph B
3=Ph A + B
4=Ph C
5=Ph A + C
6=Ph B + C
7=Ph A + B + C
7=Ph A + B + C
Monitored voltage phase
Phase mode
1=Three Phase
2=Single Phase
2=Single Phase
Three/Single phase mode
Section 10
1MRS758755 A
Power quality measurement functions
694
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...