In the three-phase voltage measurement function VMMXU the
supervision functions are based on the phase-to-phase voltages.
However, the phase-to-earth voltage values are also reported with the
phase-to-phase voltages.
GOOSE is an event based protocol service. Analog GOOSE uses the
same event generation functions as vertical SCADA communication
for updating the measurement values. Update interval of 500 ms is
used for data that do not have zero-point clamping, deadband
supervision or limit value supervision.
Zero-point clamping
A measured value under the zero-point clamping limit is forced to zero. This allows
the noise in the input signal to be ignored. The active clamping function forces both
the actual measurement value and the angle value of the measured signal to zero. In the
three-phase or sequence measuring functions, each phase or sequence component has
a separate zero-point clamping function. The zero-value detection operates so that
once the measured value exceeds or falls below the value of the zero-clamping limit,
new values are reported.
Table 563:
Zero-point clamping limits
Function
Zero-clamping limit
Three-phase current measurement (CMMXU)
1% of nominal (In)
Three-phase voltage measurement (VMMXU)
1% of nominal (Un)
Residual current measurement (RESCMMXU)
1% of nominal (In)
Residual voltage measurement (RESVMMXU)
1% of nominal (Un)
Phase sequence current measurement (CSMSQI) 1% of the nominal (In)
Phase sequence voltage measurement
(VSMSQI)
1% of the nominal (Un)
Three-phase power and energy measurement
(PEMMXU)
1.5% of the nominal (Sn)
When the frequency measurement function FMMXU is unable to
measure the network frequency in the undervoltage situation, the
measured values are set to the nominal and also the quality
information of the data set accordingly. The undervoltage limit is
fixed to 10 percent of the nominal for the frequency measurement.
Limit value supervision
The limit value supervision function indicates whether the measured value of
X_INST
exceeds or falls below the set limits. The measured value has the
corresponding range information
X_RANGE
and has a value in the range of 0 to 4:
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
555
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...