![ABB RELION Series Скачать руководство пользователя страница 605](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191605.webp)
The disturbance recorder follows the 1999 version of the
COMTRADE standard and uses the binary data file format.
8.2.5
Settings
Table 622:
RDRE Non-group general settings
Parameter
Values (Range) Unit
Step
Default
Description
Operation
1=on
5=off
1
1=on
Disturbance
recorder on/off
Record length
10...500
fundamental
cycles
1
50
Size of the
recording in
fundamental
cycles
Pre-trg length
0...100
%
1
50
Length of the
recording
preceding the
triggering
Operation
mode
1=Saturation
2=Overwrite
1
1
Operation
mode of the
recorder
Exclusion time 0...1 000 000
ms
1
0
The time
during which
triggerings of
same type are
ignored
Storage rate
32, 16, 8
samples per
fundamental
cycle
32
Storage rate
of the
waveform
recording
Periodic trig
time
0...604 800
s
10
0
Time between
periodic
triggerings
Stor. mode
periodic
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for periodic
triggering
Stor. mode
manual
0=Waveform
1=Trend /
cycle
1
0
Storage mode
for manual
triggering
1MRS758755 A
Section 8
Measurement functions
REC615 and RER615
599
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...