Table 502:
CCBRBRF Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
CB fault delay
0...60000
ms
10
5000
Circuit breaker faulty delay
Measurement mode
2=DFT
3=Peak-to-Peak
3=Peak-to-Peak
Phase current measurement mode of
function
Trip pulse time
0...60000
ms
10
200
Pulse length of retrip and backup trip
outputs
Start latching mode
1=Rising edge
2=Level sensitive
1=Rising edge
Start reset delayed or immediately
5.2.8
Monitored data
Table 503:
CCBRBRF Monitored data
Name
Type
Values (Range)
Unit
Description
CCBRBRF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
5.2.9
Technical data
Table 504:
CCBRBRF Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Operate time accuracy
±1.0% of the set value or ±20 ms
Reset time
Typically 40 ms
Retardation time
<20 ms
5.2.10
Technical revision history
Table 505:
CCBRBRF Technical revision history
Technical revision
Change
B
Default trip pulse time changed to 150 ms
C
Added new setting parameter
Start latching mode.
Maximum value changed to 2.00 xIn for the
Current value setting.
D
Internal improvement.
E
Maximum value for
Current value and Current
value Res changed from “1.00 x In” to “2.00 x In”.
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
475
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...