Section 12
Requirements for measurement
transformers
12.1
Current transformers
12.1.1
Current transformer requirements for overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be
chosen carefully. The distortion of the secondary current of a saturated CT may
endanger the operation, selectivity, and co-ordination of protection. However, when
the CT is correctly selected, a fast and reliable short circuit protection can be enabled.
The selection of a CT depends not only on the CT specifications but also on the
network fault current magnitude, desired protection objectives, and the actual CT
burden. The protection settings of the protection relay should be defined in accordance
with the CT performance as well as other factors.
12.1.1.1
Current transformer accuracy class and accuracy limit factor
The rated accuracy limit factor (F
n
) is the ratio of the rated accuracy limit primary
current to the rated primary current. For example, a protective current transformer of
type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For protective
current transformers, the accuracy class is designed by the highest permissible
percentage composite error at the rated accuracy limit primary current prescribed for
the accuracy class concerned, followed by the letter "P" (meaning protection).
Table 712:
Limits of errors according to IEC 60044-1 for protective current transformers
Accuracy class
Current error at
rated primary
current (%)
Phase displacement at rated primary
current
Composite error at
rated accuracy limit
primary current (%)
minutes
centiradians
5P
±1
±60
±1.8
5
10P
±3
-
-
10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent
protection. The 5P class provides a better accuracy. This should be noted also if there
are accuracy requirements for the metering functions (current metering, power
metering, and so on) of the protection relay.
The CT accuracy primary limit current describes the highest fault current magnitude
at which the CT fulfils the specified accuracy. Beyond this level, the secondary current
1MRS758755 A
Section 12
Requirements for measurement transformers
REC615 and RER615
761
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...