![ABB RELION Series Скачать руководство пользователя страница 469](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191469.webp)
It is recommended to use the second harmonic and the waveform
based inrush blocking from the TR2PTDF function, if available.
5.1.5
Application
Transformer protections require high stability to avoid tripping during magnetizing
inrush conditions. A typical example of an inrush detector application is doubling the
start value of an overcurrent protection during inrush detection.
The inrush detection function can be used to selectively block overcurrent and earth-
fault function stages when the ratio of second harmonic component over the
fundamental component exceeds the set value.
Other applications of this function include the detection of inrush in lines connected
to a transformer.
A070695 V4 EN
Figure 236:
Inrush current in transformer
It is recommended to use the second harmonic and the waveform
based inrush blocking from the transformer differential protection
function TR2PTDF, if available.
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
463
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...