The
WARNING
output in the receiver is activated if the synchronization accuracy of
the sender or the receiver is worse than 4 μs. The output is held on for 10 seconds after
the synchronization accuracy returns within limits.
The
WARNING
output is always internally active whenever the
ALARM
output is
active.
3.13.4.4
Signals
Table 49:
RESTVTR Input signals
Name
Type
Default
Description
Uo
INT32-UL0
0
IEC61850-9-2 residual
voltage
Table 50:
RESTVTR Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm
WARNING
BOOLEAN
Warning
3.13.4.5
Settings
Table 51:
RESTVTR Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Primary voltage
0.100...440.000
kV
0.001
11.547
Primary voltage
Secondary voltage
60...210
V
1
100
Secondary voltage
Amplitude Corr
0.9000...1.1000
0.0001
1.0000
Amplitude correction
Angle correction
-20.0000...20.0000
deg
0.0001
0.0000
Angle correction factor
3.13.4.6
Monitored data
Monitored data is available in three locations.
•
Monitoring/I/O status/Analog inputs
•
Monitoring/IED status/SMV traffic
•
Monitoring/IED status/SMV accuracy
3.14
GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Section 3
1MRS758755 A
Basic functions
106
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...