shows voltage dip operational regions. In
, only one voltage dip/
swell/Int set is drawn, whereas in this figure there are three sub-limits for the dip
operation. When
Voltage dip set 3
is undershot, the corresponding
ST_x
and also the
DIPST
outputs are activated. When the TRMS voltage magnitude remains between
Voltage dip set 2
and
Voltage dip set 1
for a period longer than
VVa dip time 2
(shorter
time than
VVa dip time 3
), a momentary dip event is detected. Furthermore, if the
signal magnitude stays between the limits longer than
VVa dip time 3
(shorter time
than
VVa Dur max
), a temporary dip event is detected. If the voltage remains below
Voltage dip set 1
for a period longer than
VVa dip time 1
but a shorter time than
VVa
dip time 2
, an instantaneous dip event is detected.
For an event detection, the
OPERATE
output is always activated for one task cycle.
The corresponding counter and only one of them (INSTDIPCNT, MOMDIPCNT or
TEMPDIPCNT) is increased by one. If the dip limit undershooting duration is shorter
than
VVa dip time 1
,
VVa swell time 1
or
VVa Int time 1
, the event is not detected at all,
and if the duration is longer than
VVa Dur Max
, MAXDURDIPCNT is increased by
one but no event detection resulting in the activation of the
OPERATE
output and
recording data update takes place. These counters are available through the monitored
data view on the LHMI or through tools via communications. There are no phase-
segregated counters but all the variation detections are registered to a common time/
magnitude-classified counter type. Consequently, a simultaneous multiphase event,
that is, the variation-type event detection time moment is exactly the same for two or
more phases, is counted only once also for single-phase power systems.
Voltage dip set 1
Voltage dip set 2
Voltage dip set 3
Voltage
xUref
Time (ms)
0
0
VVa Dur Max
VVa dip time 3
VVa dip time 1
VVa dip time 2
1.00
Instantaneous
dip
Temporary
dip
Momentary
dip
Maximum duration
dip
GUID-0D3F6D81-F905-4D8D-A579-836EF7BB6773 V1 EN
Figure 363:
Voltage dip operational regions
In
, the corresponding limits regarding the swell operation are provided
with the inherent magnitude limit order difference. The swell functionality principle
is the same as for dips, but the different limits for the signal magnitude and times and
the inherent operating zone change (here,
Voltage swell set x
> 1.0 xUn) are applied.
Section 10
1MRS758755 A
Power quality measurement functions
684
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...