Table 733:
Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Current inputs
Rated current, I
n
0.2/1 A
1)
1/5 A
2)
Thermal withstand capability
•
Continuously
4 A
1)
20 A
•
For 1 s
100 A
1)
500 A
Dynamic current withstand
•
Half-wave value
250 A
1)
1250 A
Input impedance
<100 mΩ
1)
<20 mΩ
Voltage inputs
Rated voltage
60...210 V AC
Voltage withstand
•
Continuous
240 V AC
•
For 10 s
360 V AC
Burden at rated voltage
<0.05 VA
1) Ordering option for residual current input
2) Residual current and/or phase current
Table 734:
Energizing inputs of SIM0001
Description
Value
Voltage sensor input
Rated voltage
5 kV...38 kV
1)
Continuous voltage
withstand
125 V AC
2)
Input impedance at 50/60
Hz
1 MΩ
3)
Voltage inputs
Rated voltage
60...210 V AC
Voltage withstand
•
Continuous
240 V AC
•
For 10 s
360 V AC
Burden at rated voltage
<0.05 VA
1) This range is covered with a sensor division ratio of 10 000:1 if the input type is set as CVD sensor.
2) Test to this voltage
3) Neutral input impedance is close to zero
Section 14
1MRS758755 A
Technical data
782
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...