![ABB RELION Series Скачать руководство пользователя страница 584](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191584.webp)
Name
Type
Values (Range)
Unit
Description
I1_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Positive sequence
current amplitude range
I0_INST
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, instantaneous
value
I0_ANGL
FLOAT32
-180.00...180.00
deg
Zero sequence current
angle
I0_DB
FLOAT32
0.00...40.00
xIn
Zero sequence current
amplitude, reported value
I0_RANGE
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Zero sequence current
amplitude range
8.1.9.6
Technical data
Table 604:
CSMSQI Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f/f
n
= ±2 Hz
±1.0% or ±0.002 × I
n
at currents in the range of 0.01...4.00 × I
n
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
8.1.9.7
Technical revision history
Table 605:
CSMSQI Technical revision history
Technical revision
Change
A
-
B
Sequence current angle values added to the
Monitored data view.
C
Internal improvement.
8.1.10
Sequence voltage measurement VSMSQI
8.1.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Sequence voltage measurement
VSMSQI
U1, U2, U0
V1, V2, V0
Section 8
1MRS758755 A
Measurement functions
578
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...