A070877 V1 EN
Figure 326:
Master and slave scheme
If the AR unit is defined as a master by setting its terminal priority to high:
•
The unit activates the
CMD_WAIT
output to the low priority slave unit whenever
a shot is in progress, a reclosing is unsuccessful or the
BLK_RCLM_T
input is
active
•
The
CMD_WAIT
output is reset one second after the reclose command is given or
if the sequence is unsuccessful when the reclaim time elapses.
If the AR unit is defined as a slave by setting its terminal priority to low:
•
The unit waits until the master releases the
BLK_RECL_T
input (the
CMD_WAIT
output in the master). Only after this signal has been deactivated, the reclose time
for the slave unit can be started.
•
The slave unit is set to a lockout state if the
BLK_RECL_T
input is not released
within the time defined by the
Max wait time
setting , which follows the initiation
of an autoreclosing shot.
If the terminal priority of the AR unit is set to "none", the AR unit skips all these
actions.
9.4.3.4
Thermal overload blocking
An alarm or start signal from the thermal overload protection (T1PTTR) can be routed
to the input
BLK_THERM
to block and hold the reclose sequence. The
BLK_THERM
signal does not affect the starting of the sequence. When the reclose time has elapsed
and the
BLK_THERM
input is active, the shot is not ready until the
BLK_THERM
input
deactivates. Should the
BLK_THERM
input remain active longer than the time set by
the setting
Max Thm block time
, the AR function goes to lockout.
If the
BLK_THERM
input is activated when the auto wait timer is running, the auto
wait timer is reset and the timer restarted when the
BLK_THERM
input deactivates.
9.4.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off". Setting
Operation
to "Off" resets
non-volatile counters.
The reclosing operation can be enabled and disabled with the
Reclosing operation
setting. This setting does not disable the function, only the reclosing functionality. The
1MRS758755 A
Section 9
Control functions
REC615 and RER615
633
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...