active for the time set with the
Trip pulse time
setting or the time the circuit
breaker is in the closed position, whichever is longer.
•
If
CB failure mode
is set to "Both",
TRRET
is activated when either of the
"Breaker status" or "Current" mode condition is satisfied.
•
If
CB fail retrip mode
is set to the "Without check" mode,
TRRET
is activated
once the timer 1 is activated without checking the current level. The
TRRET
output remains active for a fixed time set with the
Trip pulse time
setting.
The activation of the
BLOCK
input or the
CB_FAULT_AL
output deactivates the
TRRET
output.
POSCLOSE
I >
From Level detector 1
Timer 1 elapsed
From Timer 1
OR
AND
AND
CB fail retrip mode
”Without check”
CB fail retrip mode
”Current check”
CB failure mode ”Current”
CB failure mode ”Breaker
status”
CB failure mode ”Both”
AND
AND
AND
OR
OR
AND
TRRET
BLOCK
CB_FAULT_AL
From Timer 3
GUID-BD64DEDB-758C-4F53-8287-336E43C750F2 V2 EN
Figure 241:
Retrip logic
Backup trip logic
The backup trip logic provides the
TRBU
output which can be used to trip the upstream
backup circuit breaker when the main circuit breaker fails to clear the fault. The
backup trip logic is activated by the timer 2 module or timer-enabling signal from the
start logic module (rising edge of the
START
input detected), and simultaneously
CB_FAULT_AL
is active. The operation of the backup logic depends on the
CB
failure mode
setting.
•
If the
CB failure mode
is set to "Current", the activation of
TRBU
depends on the
CB failure trip mode
setting.
•
If
CB failure trip mode
is set to "1 out of 3", the failure detection is based
on any of the phase currents exceeding the
Current value
setting. Once
TRBU
is activated, it remains active for the time set with the
Trip pulse time
setting or until the values of all the phase currents drop below the
Current
value
setting, whichever takes longer.
•
If
CB failure trip mode
is set to "1 out of 4", the failure detection is based
on either a phase current or a residual current exceeding the
Current value
or
Current value Res
setting respectively. Once
TRBU
is activated, it
Section 5
1MRS758755 A
Protection related functions
470
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...