"Single Phase". For the selection "Three Phase" of
Phase mode
, no event indication or
any activation takes place due to a non-active phase.
U_A
U_C
U_B
ST_B
ST_C
ST_A
DIPST
INTST
SWELLST
SWELLOPR
INTOPR
DIPOPR
Voltage Int set
Voltage dip set
Voltage swell set
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
GUID-0657A163-7D42-4543-8EC8-3DF84E2F0BF5 V1 EN
Figure 367:
Concurrent dip and swell when Phase mode is "Single Phase"
In
, one phase is in dip and two phases have a swell indication. For the
Phase Mode
value "Three Phase", the activation occurs only when all the phases are
active. Furthermore, both swell and dip variation event detections take place
simultaneously. In case of a concurrent voltage dip and voltage swell, both
SWELLCNT and DIPCNT are incremented by one.
shows that for the
Phase Mode
value "Three Phase", two different
time moment variation event swell detections take place and, consequently, DIPCNT
is incremented by one but SWELLCNT is totally incremented by two. Both in
it is assumed that variation durations are sufficient for detections
to take place.
Section 10
1MRS758755 A
Power quality measurement functions
688
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...