![ABB RELION Series Скачать руководство пользователя страница 132](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191132.webp)
Table 98:
MAX3 Output signal
Name
Type
Description
OUT
FLOAT32
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.16.1.6
MIN3 function block
Function block
GUID-40218B77-8A30-445A-977E-46CB8783490D V1 EN
Figure 70:
Function block
Functionality
The minimum function MIN3 selects the minimum value from three analog values.
Disconnected inputs and inputs whose quality is bad are ignored. If all inputs are
disconnected or the quality is bad, MIN3 output value is set to 2^21.
Signals
Table 99:
MIN3 Input signals
Name
Type
Default
Description
IN1
FLOAT32
0
Input signal 1
IN2
FLOAT32
0
Input signal 2
IN3
FLOAT32
0
Input signal 3
Table 100:
MIN3 Output signal
Name
Type
Description
OUT
FLOAT32
Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
Section 3
1MRS758755 A
Basic functions
126
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...