General output
U_DEAD
is activated when setting
Num of phases
matches the number
of phases where voltage is below the set low level setting.
U_DEAD
output is
deactivated immediately after voltage dead condition is no longer met.
The activation of the
BLOCK
input deactivates all outputs.
6.4.5
Application
PHSVPR can be used to detect which one of the MV feeders is energized for feeding
the MV/LV transformer. This can reduce the needed time to restore the power after a
fault occurs in the distribution network and power needs to be manually re-routed.
GUID-9CD263BF-4825-4D73-89F3-86750F87564F V1 EN
Figure 278:
Detect live line to feed MV/LV transformer
PHSVPR can be used in addition to the other indications to detect if it is safe to start
working on the line (for example service work).
Never use PHSVPR as the only indication to check if the line is dead.
If the protection relay is used for the fault indication purposes only, then there might
be need to confirm the upstream breaker tripping. PHSVPR can be used for this
purpose together with protection and generic counter functions.
Section 6
1MRS758755 A
Supervision functions
532
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...