The activation of the
WARNING
and
ALARM
outputs depends on the
Operating time
mode
setting. Both
WARNING
and
ALARM
occur immediately after the conditions are
met if
Operating time mode
is set to “Immediate”. If
Operating time mode
is set to
“Timed Warn”,
WARNING
is activated within the next 24 hours at the time of the day
set using the
Operating time hour
setting. If
Operating time mode
is set to “Timed
Warn Alm”, the
WARNING
and
ALARM
outputs are activated at the time of day set
using
Operating time hour
.
The
Operating time hour
setting is used to set the hour of day in
Coordinated Universal Time (UTC). The setting has to be adjusted
according to the local time and local daylight-saving time.
The function contains a blocking functionality. Activation of the
BLOCK
input blocks
both
WARNING
and
ALARM
.
6.3.5
Application
The machine operating time since commissioning indicates the use of the machine.
For example, the mechanical wear and lubrication requirement for the shaft bearing of
the motors depend on the use hours.
If some motor is used for long duration runs, it might require frequent servicing, while
for a motor that is not used regularly the maintenance and service are scheduled less
frequently. The accumulated operating time of a motor together with the appropriate
settings for warning can be utilized to trigger the condition based maintenance of the
motor.
The operating time counter combined with the subsequent reset of the operating-time
count can be used to monitor the motor's run time for a single run.
Both the long term accumulated operating time and the short term single run duration
provide valuable information about the condition of the machine and device. The
information can be co-related to other process data to provide diagnoses for the
process where the machine or device is applied.
6.3.6
Signals
Table 543:
MDSOPT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block input status
POS_ACTIVE
BOOLEAN
0=False
When active indicates the equipment is running
RESET
BOOLEAN
0=False
Resets the accumulated operation time to initial
value
Section 6
1MRS758755 A
Supervision functions
528
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...