![ABB RELION Series Скачать руководство пользователя страница 626](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191626.webp)
•
The measured line and bus voltages are higher than the set values of
Live bus
value
and
Live line value
(ENERG_STATE equals to "Both Live").
•
The measured bus and line frequency are both within the range of 95 to 105
percent of the value of f
n
.
•
The measured voltages for the line and bus are less than the set value of
Max
energizing V
.
In case
Syncro check mode
is set to "Syncronous", the additional conditions must be
fulfilled.
•
In the synchronous mode, the closing is attempted so that the phase difference at
closing is close to zero.
•
The synchronous mode is only possible when the frequency slip is below 0.1
percent of the value of f
n
.
•
The voltage difference must not exceed the 1 percent of the value of U
n
.
In case
Syncro check mode
is set to “Asyncronous”, the additional conditions must be
fulfilled.
•
The measured difference of the voltages is less than the set value of
Difference
voltage
.
•
The measured difference of the phase angles is less than the set value of
Difference angle
.
•
The measured difference in frequency is less than the set value of
Frequency
difference
.
•
The estimated breaker closing angle is decided to be less than the set value of
Difference angle
.
Dead line or bus value
Live line or bus value
Difference angle
U_Bus
U_Line
Difference voltage
f
U_Bus
f
U_Line
Frequency[Hz]
f
= abs(
f
U_Bus
-
f
U_Line
)
Rated frequency
Frequency deviation
=
U_Bus
-
U_Line
Difference frequency
GUID-191F6C44-7A67-4277-8AD1-9711B535F1E1 V2 EN
Figure 316:
Conditions to be fulfilled when detecting synchronism between
systems
When the frequency, phase angle and voltage conditions are fulfilled, the duration of
the synchronism conditions is checked so as to ensure that they are still met when the
condition is determined on the basis of the measured frequency and phase difference.
Depending on the circuit breaker and the closing system, the delay from the moment
Section 9
1MRS758755 A
Control functions
620
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...