quantity is compared to the
Min operate current
setting and the magnitude of the
polarizing quantity is compared to
Min operate voltage
, and if both the operating
quantity and polarizing quantity are higher than their respective limit, a valid angle is
calculated and the residual power calculation module is enabled.
The
Correction angle
setting can be used to improve the selectivity when there are
inaccuracies due to the measurement transformer. The setting decreases the operation
sector. The
Correction angle
setting should be done carefully as the phase angle error
of the measurement transformer varies with the connected burden as well as with the
magnitude of the actual primary current that is being measured. An example of how
Correction angle
alters the operating region is as shown:
-Uo (Polarizing quantity)
Backward
area
Forward
area
Io (Operating quantity)
Zero torque line
Minimum
operate current
Maximum torque line
forward direction (RCA = 0
˚
)
Correction angle
Correction angle
Forward
area
Backward
area
GUID-B420E2F4-8293-4330-A7F3-9A002940F2A4 V1 EN
Figure 191:
Definition of correction angle
The polarity of the polarizing quantity can be changed (rotated by
180°) by setting
Pol reversal
to "True" or by switching the polarity of
the residual voltage measurement wires.
Residual power calculation
The Residual power calculation module calculates the magnitude of residual power
3UoIoCosφ. Angle φ is the angle between the operating quantity and polarizing
quantity, compensated with a characteristic angle. The angle value is received from
the Directional calculation module. The Directional calculation module enables the
residual power calculation only if the minimum signal levels for both operating
quantity and polarizing quantity are exceeded. However, if the angle calculation is not
valid, the calculated residual power is zero. Residual power (RES_POWER) is
Section 4
1MRS758755 A
Protection functions
364
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...