to operate in the directional mode as non-directional, since the directional information
is invalid.
Iosin(φ) and Iocos(φ) criteria
A more modern approach to directional protection is the active or reactive current
measurement. The operating characteristic of the directional operation depends on the
earthing principle of the network. The Iosin(φ) characteristics is used in an isolated
network, measuring the reactive component of the fault current caused by the earth
capacitance. The Iocos(φ) characteristics is used in a compensated network,
measuring the active component of the fault current.
The operation criteria Iosin(φ) and Iocos(φ) are selected with the
Operation mode
setting using the values "IoSin" or "IoCos" respectively.
The angle correction setting can be used to improve selectivity. The setting decreases
the operation sector. The correction can only be used with the Iosin(φ) or Iocos(φ)
criterion. The
RCA_CTL
input is used to change the Io characteristic:
Table 326:
Relay characteristic angle control in the IoSin and IoCos operation criteria
Operation mode:
RCA_CTL
= "False"
RCA_CTL
= "True"
IoSin
Actual operation criterion:
Iosin(φ)
Actual operation criterion:
Iocos(φ)
IoCos
Actual operation criterion:
Iocos(φ)
Actual operation criterion:
Iosin(φ)
When the Iosin(φ) or Iocos(φ) criterion is used, the component indicates a forward- or
reverse-type fault through the
FAULT_DIR
and
DIRECTION
outputs, in which 1
equals a forward fault and 2 equals a reverse fault. Directional operation is not allowed
(the
Allow non dir
setting is "False") when the measured polarizing or operating
quantities are not valid, that is, when their magnitude is below the set minimum
values. The minimum values can be defined with the
Min operate current
and
Min
operate voltage
settings. In case of low magnitude, the
FAULT_DIR
and
DIRECTION
outputs are set to 0 = unknown, except when the
Allow non dir
setting
is "True". In that case, the function is allowed to operate in the directional mode as
non-directional, since the directional information is invalid.
The calculated Iosin(φ) or Iocos(φ) current used in direction determination can be read
through the
I_OPER
monitored data. The value can be passed directly to a decisive
element, which provides the final start and operate signals.
The
I_OPER
monitored data gives an absolute value of the calculated
current.
The following examples show the characteristics of the different operation criteria:
Example 1.
Section 4
1MRS758755 A
Protection functions
296
REC615 and RER615
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...