Figure 249:
Functional module diagram
5.4.4.1
Phase selection logic
Identification of the faulty phases is provided by the built-in Phase Selection Logic
based on combined impedance and current criterion. Phase selection logic is virtually
setting-free and has only one parameter,
Z Max phase load
, for discriminating a large
symmetrical load from a three-phase fault. The setting
Z Max phase load
can be
calculated using the equation.
Z Max phase load
U
S
xy
=
⋅
0 8
2
.
max
GUID-9FFE90C4-0734-46B5-9D17-5A7FA6F723E6 V1 EN
(Equation 45)
U
xy
Nominal phase-to-phase voltage
S
max
Maximum three-phase load
For example, if U
xy
= 20 kV and S
max
= 1 MVA, then
Z Max phase load
= 320.0 Ω.
The identification of the faulty phases is compulsory for the correct operation of
SCEFRFLO. This is because only one of the impedance-measuring elements (fault
loops) provides the correct result for a specific fault type. A three-phase fault is an
exception and theoretically it can be calculated with any of the fault loops. The fault
loop used in the fault distance calculation is indicated in the recorded data Flt loop as
specified in
.
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
483
Technical Manual
Содержание RELION Series
Страница 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Страница 2: ......
Страница 30: ...24 ...
Страница 50: ...44 ...
Страница 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Страница 206: ...200 ...
Страница 514: ...508 ...
Страница 714: ...708 ...
Страница 786: ...780 ...
Страница 796: ...790 ...
Страница 798: ...792 ...
Страница 803: ...797 ...