GUID-C847609F-E261-4265-A1D9-3C449F8672A1 V2 EN
Figure 171:
Admittance characteristic with different operation modes when
Directional mode = "Reverse"
Timer
Once activated, the timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set with the
Operate
delay time
setting, the
OPERATE
output is activated. If the fault disappears before the
module operates, the reset timer is activated. If the reset timer reaches the value set
with the
Reset delay time
setting, the operation timer resets and the
START
output is
Section 4
1MRS758755 A
Protection functions
338
REC615 and RER615
Technical Manual