DiPro 1500 Fault messages
DiPro 1500 User Manual
103
Ch 7
1092000
Fault message for red sensors
SENSOR 6 [sensor name]
RED FAULT, THIS N/C SENSOR HAS BEEN
OPENED AT DEGREES
Problem:
A red sensor has actuated (is open to ground). When this message
appears, the angle where the condition was detected is also listed
shown on the LCD display.
Remedy:
Check for the press or equipment malfunction that the sensor was
supposed to detect. If none has occurred, check for a malfunctioning
sensor. Check for loose or detached wiring at the remote connection
box or controller. Check for a severed wire from the sensor to the RCB
or controller.
Fault message for green special sensors
SENSOR 5 SLUG DETECTION
GREEN SPECIAL FAULT, THE PRESS MADE 11
STROKES WITHOUT THIS SENSOR GOING ON
this number
varies depending
upon the number
set in Program
mode
Problem:
A green special sensor did not actuate within the maximum number of
strokes set in Programming mode (DiPro did not see a contact closure
to ground).
Remedy:
Check for the press or equipment malfunction that the sensor was
supposed to detect. Check for any cause that would keep the sensor
from going on. Make sure the maximum number is set correctl (not too
low).