Mounting
3.2 Rack
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
45
Rule
Always connect the rack to functional ground (FG). The connection to functional ground is
required to discharge interference and for EMC compatibility.
Note
Low-impedance connection to ground potential
Always make sure you have a low-impedance connection between the rack and ground
potential.
If you do not install the rack on a grounded surface, always create a low-impedance
connection to ground potential, for example, with the help of a copper braid.