Mounting
3.9 Setting the PROFIBUS DP Address and Terminating Resistor
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
65
Setting the PROFIBUS DP address at the connection module and activating the terminating resistor
1.
Remove the cap from the connection module.
2.
Set the PROFIBUS DP address using the DIP switches (see the example below).
3.
If this ET 200pro is the last node on PROFIBUS DP, enable the terminating resistor using
the DIP switch.
Note
Enable the terminating resistor to terminate the PROFIBUS DP network at this end point.
4.
Screw the cap back into the connection module.
5.
Hand-tighten the cap (minimum tightening torque 1.0 Nm).
Example
①
Enabling and disabling the terminating resistor
②
Setting PROFIBUS DP addresses 1 to 125
PROFIBUS DP address set on the DIP switch: 1 + 2 + 32 + 64 = 99
1
2
4
8
16
32
64
ON
ON
OFF
OFF
OFF
ON
ON
Note
Any modification of the PROFIBUS DP address is not validated unless you switch the
electronics/encoder power supply 1L+ off and on.
See also
Commissioning ET 200pro (Page 155)