Analog electronic modules
15.7 Parameter overview for analog electronic modules
ET 200pro distributed I/O system
426
Operating Instructions, 03/2013, A5E00335544-08
Parameters of analog output modules
Parameters
Value range
Default
Effective range
4 AO U High
Feature
4 AO I High
Feature
Group diagnostics
•
Disable
•
Enable
Disable
Module
Output type
—
•
Disabled
•
Voltage
Voltage
Channel
Output range
—
•
1 V to 5 V
•
±10 V
•
0 V to 10 V
±10 V
Channel
—
Output type
•
Disabled
•
Current
Current
Channel
—
Output range
•
4 mA to 20 mA
•
±20 mA
•
0 mA to 20 mA
4 mA to 20 mA
Channel
Diagnostics of encoder supply short-
circuit to M
1
•
Disable
•
Enable
Disable
Module
Diagnostics of
short-circuit at
outputs
---
•
Disable
•
Enable
Disable
Channel
---
Wire break
diagnostics
•
Disable
•
Enable
Disable
Channel
Response to CPU/Master STOP
•
Output at zero
current and
zero voltage
•
Hold last value
•
Output
substitute
values
Output at zero
current and zero
voltage
Module
Substitute value
Each value in the
rated and in the
overshoot/undersh
oot ranges
0
Channel
1
Diagnostics of short-circuits of the encoder supply to M is enabled alongside with the group
diagnostics function.
See also
Overview of parameters of the analog electronic modules (Page 427)