Power modules
13.1 PM-E power module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
321
Pin assignment of the load voltage supply at the CM PM PP connection module
View of the push-pull cable connector
Terminal
Description
Feed for X01 IN
Forwarding X02 OUT
1
1L+ electronics/encoder supply *
2
Ground for electronics/encoder supply 1M*
3
2L+ load voltage supply
4
Ground for load voltage supply 2M
5
Functional earth
* Terminals 1 and 2 are jumpered between X01 IN and X02 OUT in the connection module.
Block diagram
The figure below shows the block diagram of the power module PM-E
①
Connections of the 2L+ load voltage supply