Mounting
3.3 Mounting the Interface Module
ET 200pro distributed I/O system
54
Operating Instructions, 03/2013, A5E00335544-08
Procedure
1.
Snap-mount the interface module onto the rack, then slide it into the correct position.
2.
Screw-mount the Interface module onto the rack.
–
Interface modules for PROFIBUS DP (without connection module):
2 recessed head screws on the front: top and bottom, tightening torque 1.5 N/m
–
Interface module for PROFINET IO:
2 recessed head screws (for 6ES7154-4AB10-0AB0) on the front: top and bottom,
tightening torque 1.5 N/m
Figure 3-6
Mounting the interface module for PROFIBUS DP (example)
See also
Connecting the Interface Module to a CM IM DP ECOFAST Cu Connection Module
(Page 87)
Connecting the Interface Module to the CM IM DP M12, 7/8" Connection Module (Page 91)