Connection
4.11 Wiring the Electronic Module using the Connection Module
ET 200pro distributed I/O system
122
Operating Instructions, 03/2013, A5E00335544-08
4.11.3
Pin assignment for the analog electronic modules
Using the shield support
To prevent interference we recommend the following for analog electronic modules:
●
Use pre-fabricated shielded cables to the connection modules.
●
If you are fabricating your own cable, place the cable shield on the ferrous connector
enclosure or use terminal 5 for shield support purposes.
The connection module connects the cable shield with low impedance to the main ground
line.
Pin assignment of CM IO 4 x M12 connection module and 4 AI U High Feature electronic module
Note
Only the CM IO 4 x M12 connection module may be used for the electronic module.
Table 4- 22 Pin assignment of CM IO 4 x M12 with 4 AI U High Feature
View of the coupler plug
Terminal
Assignment X1 to X4
1
24V encoder supply U
S
2
Input signal DI
0
+: Connector X1
Input signal U
1
+: Connector X2
Input signal U
2
+: Connector X3
Input signal U
3
+: Connector X4
3
Encoder supply ground 1M
4
Input signal U
0
-: Connector X1
Input signal U
1
-: Connector X2
Input signal U
2
-: Connector X3
Input signal U
3
-: Connector X4
5
Functional earth (FE)
①
Shielded copper cables