Configuring
5.2 PROFINET IO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
151
5.2.5
Configuring port 1 and port 2
Introduction
The IM154-4 PN High Feature interface module can diagnose two ports: X02 P1 and
X02 P2.
Requirements
●
The ports must be configured in HW Config.
●
The port diagnostics must be released.
Configuring the ports in HW Config
Configure both ports in HW Config in the "Properties of the IM154-4 PN High Feature port..."
dialog:
●
Addresses tab: Diagnostic address of the respective port.
●
Topology tab:
Select the fiber-optic cables in "Port Interconnection" under "Cable Designation":
POF Standard Cable GP or POF Trailing Cable.
●
Options tab:
To enable the port diagnostics, select the following for "Connection" under "Transmission
Medium/Duplex": "Automatic Settings (monitor)".
Reference
See
STEP 7
online help.