Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
443
Measuring ranges for Ni x00 standard thermal resistor
Ni x00 Standard
in °C
(1 digit = 0.1 °C)
Units
Ni x00 Standard
in °F
(1 digit = 0.1 °F)
Units
Range
Decimal Hexadecimal
Decimal Hexadecimal
> 295,0
32767
7FFF
H
> 563,0
32767
7FFF
H
Overflow
295,0
:
250,1
2950
:
2501
B86
H
:
9C5
H
563,0
:
482,1
5630
:
4821
15FE
H
:
12D5
H
Overrange
250,0
:
-60,0
2500
:
-600
9C4
H
:
FDA8
H
482,0
:
-76,0
4820
:
-760
12D4
H
:
FD08
H
Nominal range
-60,1
:
-105,0
-601
:
-1050
FDA7
H
:
FBE6
H
-76,1
:
-157,0
-761
:
-1570
FD07
H
:
F9DE
H
Underrange
< -105,0
-32768
8000
H
< -157,0
-32768
8000
H
Underflow
Measuring ranges for Ni cx00 climatic thermal resistor
Ni x00 climatic
in °C
(1 digit = 0.01 °C)
Units
Ni x00 climatic
in °F
(1 digit = 0.01 °F)
Units
Range
Decimal Hexadecimal
Decimal Hexadecimal
> 155,00
32767
7FFF
H
> 311,00
32767
7FFF
H
Overflow
155,00
:
130,01
15500
:
13001
3C8C
H
:
32C9
H
311,00
:
266,01
31100
:
26601
797C
H
:
67E9
H
Overrange
130,00
:
-60,00
13000
:
-6000
32C8
H
:
E890
H
266,00
:
-76,00
26600
:
-7600
67E8
H
:
E250
H
Nominal range
-60,01
:
-105,00
-6001
:
-10500
E88F
H
:
D6FC
H
-76,01
:
-157,00
-7601
:
-15700
E24F
H
:
C2AC
H
Underrange
< -105,00
-32768
8000
H
< -157,00
-32768
8000
H
Underflow