Alarm, error and system messages
9.2 PROFINET IO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
227
Error type
Error text
Meaning
Remedy
10110
B
22
D
Process interrupt lost
ET 200pro failed to detect a process
interrupt
Correction or coordination of the
program, process, module
11010
B
26
B
External error
Error at encoder circuit
Correct the process wiring
See also
Channel-specific diagnostic data (Page 204)
Channel diagnostics (Page 224)
9.2.5.4
Interruption of the ET 200pro backplane bus
Separate diagnostics for bus interruption: USI = W#16#0001
If the ET 200pro does not start up, the causes can include:
●
One or several missing modules
●
Terminating module missing
●
Number of modules exceeds maximum configuration
●
Backplane bus fault (for example, defective bus module)
If the data exchange is interrupted, the causes can include:
●
At least two modules (compared to a missing module, this is no longer a gap, but rather a
loose backplane bus)
●
Terminating module missing
●
Backplane bus fault (for example, defective bus module)
ET 200pro backplane bus interruptions do not trigger an interrupt.
You can read this information with STEP 7 in SIMATIC Manager via "Accessible nodes" in
the "Module information" window. This requires that the programming device is available in
the PROFINET subnet. The information is displayed in text format.
See also
Identifier-related diagnostic data (Page 202)
Module status (Page 203)