Analog electronic modules
15.9 Dynamic reference temperature for the 4 AI TC High Feature electronic module
ET 200pro distributed I/O system
434
Operating Instructions, 03/2013, A5E00335544-08
Data record DS2 structure
Figure 15-7 Data record DS2 structure
Temperature unit
Decimal
Hexadecimal
Celsius (standard)
-1450 to 1550
FA56
H
to 60E
H
Fahrenheit (standard)
-2290 to 3110
F70E
H
to C26
H
Kelvin (standard)
1282 to 4282
502
H
to 10BA
H
Celsius (climatic)
-14500 to 15500
C75C
H
to 3C8C
H
Fahrenheit (climatic)
-22900 to 31100
A68C
H
to 797C
H
Kelvin (climatic)
12815 to 32760
23FF
H
to 7FF8
H