Analog electronic modules
15.7 Parameter overview for analog electronic modules
ET 200pro distributed I/O system
422
Operating Instructions, 03/2013, A5E00335544-08
Parameters
Value range
Default
Effective range
Measuring range
•
150 Ω
•
300 Ω
•
600 Ω
•
3000 Ω
•
Pt100 climatic range
•
Ni100 climatic range
•
Pt100 standard range
•
Ni100 standard range
•
Pt500 standard range
•
Pt1000 standard range
•
Ni1000 standard range
•
Pt200 climatic range
•
Pt500 climatic range
•
Pt1000 climatic range
•
Ni1000 climatic range
•
Pt200 standard range
•
Ni120 standard range
•
Ni120 climatic range
•
Ni200 standard range
•
Ni200 climatic range
•
Ni500 standard range
•
Ni500 climatic range
Pt100 standard
Channel
Temperature coefficient
•
Pt 0.003851
1
•
Pt 0.003916
•
Pt 0.003902
•
Pt 0.003920
•
Pt 0.003850
•
Ni 0.006180
•
Ni 0.006720
Pt 0.003851
1
Channel
1