Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
440
Operating Instructions, 03/2013, A5E00335544-08
Current measuring range: 0 to 20 mA
Measuring range
0 mA to 20 mA
Units
Range
Decimal
Hexadecimal
> 23.52 mA
32767
7FFF
H
Overflow
23.52 mA
32511
7EFF
H
Overrange
27649
6C01
H
20 mA
27648
6C00
H
Nominal range
15 mA
20736
5100
H
723.4 nA
1
0001
H
0 mA
0
0000
H
- 1
FFFF
H
Underrange
-3.52 mA
-4864
ED00
H
< -3.52 mA
32768
8000
H
Underflow
Current measuring range: 4 to 20 mA
Measuring range
4 mA to 20 mA
Units
Range
Decimal
Hexadecimal
> 22.81 mA
32767
7FFF
H
Overflow
22.81 mA
32511
7EFF
H
Overrange
27649
6C01
H
20 mA
27648
6C00
H
Nominal range
16 mA
20736
5100
H
4 mA + 578.7 nA
1
0001
H
4 mA
0
0000
H
- 1
FFFF
H
Underrange
1.185 mA
-4864
ED00
H
< 1.185 mA
32767
7FFF
H
Wire break
-32768
8000
H
Underflow