Connection
4.7 Connecting the Interface Module to the CM IM DP M12, 7/8" Connection Module
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
91
4.7
Connecting the Interface Module to the CM IM DP M12, 7/8"
Connection Module
Introduction
You connect the power supplies and PROFIBUS DP to the CM IM DP M12, 7/8" connection
module.
DP1 X03
M12 circular socket connector (with male contact insert) for feeding PROFIBUS DP
DP2 X04
M12 circular socket connector (with female contact insert) for forwarding
PROFIBUS DP
X01 DC 24V 7/8" circular socket connector (with male contact insert) for feeding the 1L+
electronics/
encoder supply and 2L+ load voltage supply
X02 DC 24V 7/8" circular socket connector (with female contact insert), for looping the 1L+
electronics/
encoder supply and 2L+ load voltage supply
Requirements
●
The interface module (including the bus module) and the connection module are mounted
on the rack.
●
You have set the PROFIBUS DP address on the connection module according to your
configuration.
●
The terminating resistor must be activated if no loop cables are connected.
Required tools
Screwdriver and stripping tool for wiring the M12 and 7/8" cable connectors, if you are
fabricating your own cables.