12.2 Interface modules for PROFINET IO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
313
Pin assignment of PROFINET IO and supply voltages on the CM IM PN PP Cu connection module
Note
If you deactivate the "Autonegotiation" function in STEP 7, you must observe the changed
pin assignment.
View of the push-pull cable connector
Terminal
Assignment
Push-pull cable connector (1L+ and 2L+ supply voltages)
X03 DC 24V for feeding
X04 DC 24V for looping
1
1L+ electronics/encoder supply
2
Ground for electronics/encoder supply 1M
3
2L+ load voltage supply
4
Ground for load voltage supply 2M
5
Functional earth (FE)
Push-pull cable connector (RJ45)
X02 P1 for connecting
PROFINET
X02 P2 for connecting
PROFINET
1
Transmit Data+ TD
Receive Data+ RD
2
Transmit Data- TD_N
Receive Data- RD_N
3
Receive Data+ RD
Transmit Data+ TD
4
Ground GND
5
Ground GND
6
Receive Data- RD_N
Transmit Data- TD_N
7
Ground GND
8