Configuring
5.2 PROFINET IO
ET 200pro distributed I/O system
148
Operating Instructions, 03/2013, A5E00335544-08
5.2.2
Configuring by Means of GSD File
Introduction
The GSD file allows you to configure ET 200pro in STEP 7 V5.3 SP 2 or higher. For this
purpose, the GSD file must be installed in the configuration software beforehand.
Requirements
You require a GSD file, available for download from the Internet at:
GSD file (
http://support.automation.siemens.com
IM 154-4 PN High Feature interface module:
GSDML-V2.2-siemens-et200pro-"date in yyyymmdd format".xml
Configuring ET 200pro on PROFINET IO in STEP 7
1.
Start STEP 7, then select Options > Install New GSD File in HW Config.
2.
Select the GSDML file to install from the next dialog box, then confirm with OK. Result:
ET 200pro appears in the PROFINET IO folder of the hardware catalog.
3.
The further procedure is the same as in Configuring in STEP 7 (Page 147).
See also
Commissioning ET 200pro (Page 155)