Interface modules
12.1 Interface modules for PROFIBUS DP
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
293
Technical specifications
Status, interrupts, diagnostics
Interrupts
Yes
Diagnostic function
Yes
•
Group error
Red "SF" LED
•
PROFIBUS DP monitoring
Red "BF" LED
•
Monitoring of the supply voltage of the
electronics
Green "ON" LED
•
Monitoring of the rated load voltage 2L+
Green "DC 24V" LED (integrated power module)
Acyclic data traffic class 2 services (PG/OP)
The IM 154-1 DP interface module supports 3 connections via class 2 services (PG/OP).
Configuration with more than 240 bytes of parameter data
For configurations with STEP 7 V5.5 or higher, it is possible to operate the IM 151-1 DP
(6ES7154-1AA01-0AB0 or higher) in DPV1 mode with more than 240 byte of parameter
data.
A configuration based on the GSD file does not offer this possibility.
Note
If the parameter length exceeds 240 byte, a longer station startup time is to be expected.
See also chapter Parameter assignment dependencies (Page 304).
See also
Connection module CM IM DP Direct for interface modules (Page 249)
CM IM DP ECOFAST Cu connection module for interface modules (Page 251)
CM IM DP M12 connection module, 7/8" for interface modules (Page 253)
Electrical Configuration of ET 200pro (Page 71)