Interface modules
12.1 Interface modules for PROFIBUS DP
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
299
Technical specifications
Technical specifications
Dimensions and weight
Dimensions W x H x D (mm)
90 × 130 × 59.3
Weight
Approx. 375 g
Module-specific data
Transfer rate
9.6; 19.2; 45.45; 93.75; 187.5; 500 kBaud,
1.5; 3; 6; 12 Mbps
Bus protocol
PROFIBUS DP
Interface
RS 485
SYNC capability
Yes
FREEZE capability
Yes
Manufacturer ID
8119
H
Direct data exchange
Yes
Isochronous mode
No
Voltages and currents
Rated supply voltage of the electronic
components (1L+)
24 V DC
•
Reverse polarity protection
Yes; against destruction
•
Short-circuit protection
Yes; with replaceable fuses
•
Feed current 1L+
Max. 5 A; per ET 200pro
Rated load voltage 2L+
24 V DC(integrated power module)
•
Reverse polarity protection
Yes; against destruction
•
Short-circuit protection
Yes, for the potential group
•
Feed current 2L+
Max. 10 A per ET 200pro
Current consumption
From rated supply voltage (1L+)
Typ. 200 mA
Power loss of the module
Typ. 5 W
Isolation
Isolation tested with
500 V DC
Electrical isolation
•
Between the backplane bus and supply
voltages (1L+, 2L+)
Yes
•
Between PROFIBUS DP and supply
voltages (1L+, 2L+)
Yes
•
Between electronics and supply voltages
(1L+, 2L+)
Yes
Permitted potential difference
75 V DC, 60 V AC