Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
444
Operating Instructions, 03/2013, A5E00335544-08
Measuring range for type B thermocouple
Type B in
°C
Units
Type B in
°F
Units
Type B in K Units
Range
Decimal Hexadeci
mal
Decimal Hexadeci
mal
Decimal Hexadeci
mal
> 2070,0
32767
7FFF
H
> 3276,6
32767 7FFF
H
> 2343,2
32767
7FFF
H
Overflow
2070,0
:
1820,1
20700
:
18201
50DC
H
:
4719
H
3276,6
:
2786,6
32766
:
27866
7FFE
H
:
6CDA
H
2343,2
:
2093,3
23432
:
20933
5B88
H
:
51C5
H
Overrange
1820,0
:
0,00
18200
:
0
4718
H
:
0000
H
2786,5
:
32,0
27865
:
320
6CD9
H
:
0140
H
2093,2
:
273,2
20932
:
2732
51C4
H
:
0AAC
H
Nominal
range
< -0,0
-32768 8000
H
< 32,0
-32768 8000
H
< 273,2
-32768 8000
H
Underflow
Measuring range for type E thermocouple
Type E in
°C
Units
Type E in
°F
Units
Type E in K Units
Range
Decimal Hexadeci
mal
Decimal Hexadeci
mal
Decimal Hexadeci
mal
> 1200,0
32767
7FFF
H
> 2192,0
32767
7FFF
H
> 1473,2
32767
7FFF
H
Overflow
1200,0
:
1000,1
12000
:
10001
2EE0
H
:
2711
H
2192,0
:
1832,1
21920
:
18321
55A0
H
:
4791
H
1473,2
:
1273,3
14732
:
12733
398C
H
:
31BD
H
Overrange
1000,0
:
-270,0
10000
:
-2700
2710
H
:
F574
H
1832,0
:
-454,0
18320
:
-4540
4790
H
:
EE44
H
1273,2
:
3,2
12732
:
32
31BC
H
:
0020
H
Nominal
range
< -270,0
-32767 8000
H
< -454,0
-32768 8000
H
<3,2
-32768 8000
H
Underflow
Measuring range for type J thermocouple
Type J in
°C
Units
Type J in °F Units
Type J in K Units
Range
Decimal Hexadeci
mal
Decimal Hexadeci
mal
Decimal Hexadeci
mal
> 1450,0
32767
7FFF
H
> 2642,0
32767
7FFF
H
> 1723,2
32767
7FFF
H
Overflow
1450,0
:
1200,1
14500
:
12001
38A4
H
:
2EE1
H
2642,0
:
2192,1
26420
:
21921
6734
H
:
55A1
H
1723,2
:
1473,3
17232
:
14733
4350
H
:
398D
H
Overrange
1200,0
:
-210,0
12000
:
-2100
2EE0
H
:
F7CC
H
2192,0
:
-346,0
21920
:
-3460
55A0
H
:
F27C
H
1473,2
:
63,2
14732
:
632
398C
H
:
0278
H
Nominal range
< -210,0
-32768 8000
H
<-346,0
-32768 8000
H
< 63,2
-32768 8000
H
Underflow