Analog electronic modules
15.7 Parameter overview for analog electronic modules
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
419
See also
Connection module CM IO 4 x M12 for electronic modules (Page 261)
Response times for analog input modules (Page 509)
15.7
Parameter overview for analog electronic modules
Parameters for the 4 AI U High Feature, 4 AI I High Feature analog input modules
Parameters
Value range
Default
Effective range
4 AI U High
Feature
4 AI I High
Feature
Group diagnostics
•
Disable
•
Enable
Disable
Module
Process interrupt (limit value interrupt)
•
Disable
•
Enable
Disable
Channel 0
Interference frequency suppression
•
50 Hz
•
60 Hz
50 Hz
Module
Measuring method —
•
Disabled
•
Voltage
Voltage
Channel
Measuring range —
•
±5 V
•
1 V to 5 V
•
0 V to 10 V
•
±10 V
±10 V
Channel
—
Measuring method
•
Disabled
•
Current
(4 DMU)
•
Current
(2 DMU)
2
Current (4 DMU)
Channel
—
Measuring range
•
0 mA to 20 mA
•
4 mA to 20 mA
•
±20 mA
4 mA to 20 mA
Channel
Diagnostics of encoder supply short-
circuit to M
1
•
Disable
•
Enable
Disable
Module
Short-circuit diagnostics
3
•
Disable
•
Enable
Disable
Channel
Diagnostics of wire break
3
•
Disable
•
Enable
Disable
Channel