Alarm, error and system messages
9.2 PROFINET IO
ET 200pro distributed I/O system
226
Operating Instructions, 03/2013, A5E00335544-08
9.2.5.3
Error types for electronic modules
Error types and remedies
The table below shows the error types for electronic modules.
Table 9- 8
Error types for electronic modules
Error type
Error text
Meaning
Remedy
00001
B
1
D
Short-circuit
•
Short-circuit to M potential at
encoder line
•
Short-circuit to M potential at
output line
•
Short-circuit to P potential or
ground at output line
•
Load impedance too low
•
Correct the process wiring
•
Check encoder or actuator
00110
B
6
D
Cable break
•
Signal line to encoder or actuator
interrupted
•
Defective encoder or actuator
•
Load impedance too high
•
Correct the process wiring
•
Replace the encoder or actuator
•
Use an encoder with higher
impedance
•
Use an actuator with lower load
00111
B
7
D
Violation of upper limit The value is above the overrange
•
Correct the module/encoder
tuning
•
Change the measuring range in
the parameter assignment
01000
B
8
D
Violation of lower limit
The value is below the underrange
•
Correct the module/encoder
tuning
•
Change the measuring range in
the parameter assignment
01001
B
9
D
Error
Internal module error (diagnostic
message on channel 0 applies to the
entire module)
Replace the module
Short circuit to M. The
electronic/encoder supply is short-
circuited to M potential (only for the
PM-O DC 2x24V outgoing module)
Correct the process wiring
10000
B
16
D
Parameter assignment
error
Module not parameterized
Correct the parameters
10001
B
17
D
Encoder voltage or load
voltage is missing
•
Supply voltages missing or too
low
•
Load voltage supply missing or
too low
•
Check the supply voltages
•
Check the load voltage supply
•
Correct the process wiring
10101
B
21
D
Reference channel
error
Measuring line for compensation
interrupted
Correct the process wiring
Data record DS2 incorrect
Check data record DS2
Timeout for "Dynamic ref. temp."
Send DS2