Digital electronic modules
14.9 Overview of parameters of the digital electronic modules
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
375
14.9
Overview of parameters of the digital electronic modules
Parameters of 8 DI DC 24V
Parameters
Value range
Default
Effective range
Diagnostics for short circuit to M
•
Disable
•
Enable
Disable
Module
Parameters of 8 DI DC 24V High Feature
Parameters
Value range
Default
Effective range
Group diagnostics
•
Disable
•
Enable
Disable
Module
Hardware interrupt enable
•
Disable
•
Enable
Disable
Module
Input delay (ms)
•
0.5
•
3
•
15
•
20
3
Module
Diagnostics: Short-circuit to M 24 V
encoder supply (channels 0 to 7 *)
•
Disable
•
Enable
Disable
Channel
Diagnostics: Wire break
(channels 0 to 7)
•
Disable
•
Enable
Disable
Channel
Hardware interrupt at rising edge
(channels 0 to 5)
•
Disable
•
Enable
Disable
Channel
Hardware interrupt at falling edge
(channels 0 to 5)
•
Disable
•
Enable
Disable
Channel
* If you use the electronic module with the connection module CM IO 4xM12, channels 4 to 7 are
mapped to channels 0 to 3. A precise channel-specific diagnosis "Short-circuit to M" is not therefore
possible.