Analog electronic modules
15.11 Measuring ranges of the analog input modules in S7 format
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
439
Voltage measuring ranges: ± 5 V, ± 10 V
Measuring range ± 5 V Measuring range ± 10 V Units
Range
Decimal
Hexadecimal
> 5.879 V
> 11,759
32767
7FFF
H
Overflow
5.879 V
11,759
32511
7EFF
H
Overrange
27649
6C01
H
5 V
10 V
27648
6C00
H
Nominal range
3.750 V
7.5 V
20736
5100
H
180.850 µV
361.7 µV
1
0001
H
0 V
0 V
0
0000
H
-1
FFFF
H
-3.750 V
-7.5 V
-20736
AF00
H
-5 V
-10 V
-27648
9400
H
-27649
93FF
H
Underrange
-5.879 V
-11.759 V
-32512
8100
H
< -5.879 V
< -11.759 V
-32768
8000
H
Underflow
Voltage measuring range: ±80 mV
Measuring range ±80 mV
Units
Range
Decimal
Hexadecimal
> 94.1 mV
32767
7FFF
H
Overflow
94.1 mV
32511
7EFF
H
Overrange
27649
6C01
H
80 mV
27648
6C00
H
Nominal range
60 mV
20736
5100
H
2.89 µV
1
0001
H
0 mV
0
0000
H
-1
FFFF
H
-60 mV
-20736
AF00
H
-80 mV
-27648
9400
H
-27649
93FF
H
Underrange
-94.1 mV
-32512
8100
H
< -94.1 mV
-32768
8000
H
Underflow