Connection
4.5 Connecting the interface module to a CM IM DP Direct connection module
ET 200pro distributed I/O system
84
Operating Instructions, 03/2013, A5E00335544-08
4.5.4
Connecting PROFIBUS DP
Connecting the PROFIBUS DP cable
1.
Open the black strain relief using a crosstip screwdriver.
2.
Open the transparent insert of the insulation displacement terminal.
3.
Feed the incoming PROFIBUS DP cable into insert A/B of the insulation displacement
terminal DP1. Wire red to red, and green to green accordingly.
4.
When forwarding the PROFIBUS DP cable, terminate it at insert A/B of the insulation
displacement terminal DP2.
5.
Push the insert firmly down onto the contact.
6.
Secure the black strain relief using a crosstip screwdriver.
①
Shield support for cable
Figure 4-10 View of open PROFIBUS cable connector
Note
You may leave insulation residue in the insulation displacement terminal when you open
it. This may pose a problem the next time you connect a wire. You should thus always
ensure not to leave any insulation residue in the insulation displacement terminal when
you open it and remove the wire.